Diesel Generator Fuel Consumption Chart (Litres per Hour)
Short answer: MPS diesel generators use from 1.7 litres per hour (MPS 10, 10 kVA, at 50% load) to 529 L/hr (MPS 2500, 2,500 kVA, at its standby rating). A 500 kVA prime generator such as the MPS 550 burns 76 L/hr at 75% load and 100 L/hr at full prime load.
Fuel use of every MPS generator
Litres per hour from the MPS data sheets. Load percentages are of the prime rating. “Hours on tank” is the built-in tank divided by fuel use at 75% load; sets from 1,000 kVA up use an external fuel tank.
| Model | Standby kVA | Prime kVA | 50% load | 75% load | 100% prime | Standby load | Built-in tank (L) | Hours on tank at 75% |
|---|---|---|---|---|---|---|---|---|
| MPS 10 | 10 | 9 | 1.7 | 2.3 | 3 | 3.6 | 80 | 34.8 |
| MPS 15 | 15 | 13 | 2 | 2.8 | 3.7 | 4.1 | 80 | 28.6 |
| MPS 16.5 | 16.5 | 15 | 2.2 | 3.1 | 4.3 | 5 | 80 | 25.7 |
| MPS 17 | 17 | 15 | 2.2 | 3.1 | 4.3 | 5 | 80 | 25.7 |
| MPS 22 | 22 | 20 | 2.9 | 4 | 5.3 | – | 80 | 20.0 |
| MPS 50 | 50 | 45 | 5.8 | 8 | 10.5 | 11.7 | 90 | 11.3 |
| MPS 88 | 88 | 80 | 9.7 | 14 | 18.7 | 20.5 | 186 | 13.3 |
| MPS 110 | 110 | 100 | 11.8 | 17.1 | 22.6 | 24.9 | 186 | 10.9 |
| MPS 150 | 150 | 135 | 15.9 | 22.7 | 30.3 | 33.8 | 280 | 12.3 |
| MPS 165 | 165 | 150 | 16.4 | 24.7 | 33.4 | 36.1 | 420 | 17.0 |
| MPS 220 | 220 | 200 | 23.1 | 34.7 | 45.8 | 49.4 | 420 | 12.1 |
| MPS 275 | 275 | 230 | 27.8 | 40.4 | 54.5 | 61.1 | 480 | 11.9 |
| MPS 330 | 330 | 300 | 33 | 48 | 65 | 73 | 520 | 10.8 |
| MPS 385 | 385 | 350 | 37 | 54 | 71 | 80 | 865 | 16.0 |
| MPS 400 | 400 | 350 | 37 | 54 | 71 | 80 | 865 | 16.0 |
| MPS 440 | 440 | 400 | 43 | 62 | 81 | 90 | 865 | 14.0 |
| MPS 450 | 450 | 400 | 42 | 62 | 81 | 90 | 865 | 14.0 |
| MPS 550 | 550 | 500 | 53 | 76 | 100 | 111 | 865 | 11.4 |
| MPS 660 | 660 | 600 | 61 | 90 | 123 | 134 | 1,100 | 12.2 |
| MPS 700 | 700 | 650 | 66 | 97 | 132 | 143 | 1,100 | 11.3 |
| MPS 715 | 715 | 650 | 66 | 97 | 132 | 143 | 1,100 | 11.3 |
| MPS 770 | 770 | 700 | 76 | 108 | 145 | 160 | 1,400 | 13.0 |
| MPS 1000 | 1,000 | 900 | 98 | 143 | 195 | 218 | – | – |
| MPS 1100 | 1,100 | 1,000 | 111 | 162 | 215 | 249 | – | – |
| MPS 1650 | 1,650 | 1,500 | 153 | 226 | 297 | 331.5 | – | – |
| MPS 1875 | 1,875 | 1,710 | 175.7 | 261 | 358.2 | 397.6 | – | – |
| MPS 2000 | 2,000 | 1,850 | 185 | 277 | 383 | 424 | – | – |
| MPS 2250 | 2,250 | 2,000 | 208 | 306 | 405 | 463 | – | – |
| MPS 2500 | 2,500 | 2,250 | 246 | 349 | 470 | 529 | – | – |
How to estimate your diesel use
- Find your average load as a percentage of the generator’s prime rating.
- Read the litres per hour for that load from the chart.
- Multiply by the hours the generator runs each day. For example, the MPS 550 at 75% load for 10 hours uses about 760 litres a day.
Frequently asked questions
How much diesel does a 500 kVA generator use per hour?
The MPS 550 (550 kVA standby, 500 kVA prime) uses 53 L/hr at 50% load, 76 L/hr at 75% and 100 L/hr at 100% prime load, according to its data sheet.
How do I work out how long a generator runs on a full tank?
Divide the tank size by the fuel use at your load. The MPS 550 has a 865 litre built-in tank, so at 75% load it runs about 11.4 hours before refuelling.
Does a generator use less fuel at lower load?
Yes, but not in proportion. On the MPS data sheets, running at 50% load uses 48% to 57% of the full-load fuel, so a generator that is much too big for its load uses more diesel for each kWh it produces.
How much diesel per kWh does a generator use?
At full prime load, MPS generators use between 0.25 and 0.43 litres of diesel for each kWh they produce, depending on the model. Multiply your daily kWh by that figure for a rough daily fuel estimate.
Related guides
- Generator sizing guide: what size generator do I need?
- Diesel generator fuel consumption chart
- Silent vs open diesel generators
- Prime vs standby generator ratings
Need help choosing?