17 kVA Perkins Diesel Generator, MPS 17
The MPS 17 is a 17 kVA standby, 15 kVA prime diesel generator powered by a Perkins 403A-15G2 engine, with a Leroy Somer TAL-040-D alternator and a DSE 4520 controller. It runs at 400 V, 3 phase, 50 Hz and is available as a silent canopy or open set.

Silent and open versions


Key specifications
| Prime power | 15 kVA / 12 kW |
|---|---|
| Standby power | 17 kVA / 13 kW |
| Engine | Perkins 403A-15G2 |
| Cylinders | 3 vertical in-line |
| Aspiration | Naturally Aspirated |
| Alternator | Leroy Somer TAL-040-D |
| Controller | DSE 4520 |
| Output | 400 V, 3 phase, 50 Hz, 1500 rpm, 0.8 power factor |
| Built-in fuel tank | 80L |
| Noise level | 57.4 dB(A) ±3 dB at 7 m |
Fuel consumption
| 50% prime load | 2.2 L/hr |
|---|---|
| 75% prime load | 3.1 L/hr |
| 100% prime load | 4.3 L/hr |
| Standby load | 5 L/hr |
Dimensions and weight
| Silent canopy (L x W x H, weight) | 2,000 x 922 x 1,240 mm, 651 kg |
|---|---|
| Open set (L x W x H, weight) | 1,556 x 700 x 1,197 mm, 435 kg |
Data sheets
- MPS 17 generator data sheet MPS, PDF
- Perkins 403A-15G2 engine data sheet Perkins, PDF
- Leroy Somer TAL-040-D alternator data sheet Leroy Somer, PDF
Frequently asked questions
How much diesel does a 17 kVA generator use?
The MPS 17 uses about 4.3 litres per hour at 100% prime load and 3.1 L/hr at 75% load, according to its data sheet. Real use depends on the load.
How heavy is a 17 kVA silent generator?
The MPS 17 silent canopy version weighs 651 kg and measures 2,000 x 922 x 1,240 mm.
What is the difference between 15 kVA prime and 17 kVA standby?
Prime power is for unlimited running hours at an average load of 80% of the prime rating. Standby power is for emergency backup, limited to 500 hours a year at an average 80% of the standby rating.
Get a quote for the MPS 17
Tell us your site, load and whether you need prime or standby power. Call +971 4 874 2229 or request a quote.
Also see: all Perkins generators · prime vs standby ratings · installation, AMC and spare parts