Prime vs Standby Generator Ratings Explained
Short answer: a prime rating is the power a generator can supply for unlimited hours as your main power source. A standby rating is the higher figure it can supply only during grid outages, for up to 500 hours a year. A 450 kVA standby generator such as the MPS 450 is rated 400 kVA prime.
The difference at a glance
| Prime power (PRP) | Standby power (ESP) | |
|---|---|---|
| Use | Main power source: off-grid sites, construction, remote facilities | Backup when the grid fails: buildings, hospitals, data centres |
| Running hours | Unlimited | Up to 500 hours a year |
| Average load | Up to 80% of the prime rating over each 24 hours | Up to 80% of the standby rating over each 24 hours |
| Continuous running | Allowed | Up to 300 hours a year |
| Overload | 10% for 1 hour in every 12 hours | None |
| Rating figure | Lower | 8 to 20% higher than prime on MPS sets |
Source: rating definitions on the MPS data sheets, which use the ISO 8528-1 terms PRP and ESP.
Prime and standby ratings on MPS generators
| MPS 110 | 100 kVA prime / 110 kVA standby |
|---|---|
| MPS 220 | 200 kVA prime / 220 kVA standby |
| MPS 450 | 400 kVA prime / 450 kVA standby |
| MPS 1000 | 900 kVA prime / 1,000 kVA standby |
| MPS 2000 | 1,850 kVA prime / 2,000 kVA standby |
Which rating should you size to?
- No grid connection, or the generator runs every day: size to the prime rating.
- The generator only covers outages: size to the standby rating, but keep the real load near 70 to 80% of it.
- Critical sites such as hospitals and data centres often specify extra margin or multiple synchronized sets. Check your consultant’s specification.
Common mistakes
- Comparing a standby kVA with another supplier’s prime kVA. Always compare like with like.
- Running a standby-rated set as the main power source. It will exceed its rated hours and wear faster.
- Ignoring heat. MPS ratings are stated at 40°C air inlet temperature. Hotter plant rooms need checking with an engineer.
Frequently asked questions
Is kVA the same as kW?
No. kW is real power; kVA includes the power factor. At the standard 0.8 power factor, kW = kVA x 0.8, so a 450 kVA standby set gives 360 kW.
Can I run a standby generator continuously?
Only for up to 300 hours a year, within the 500-hour annual limit. For longer running, choose a set sized on its prime rating.