770 kVA Perkins Diesel Generator, MPS 770
The MPS 770 is a 770 kVA standby, 700 kVA prime diesel generator powered by a Perkins 2806A-E18TTAG4 engine, with a Leroy Somer TAL-049-B alternator and a DSE 7320 controller. It runs at 400 V, 3 phase, 50 Hz and is available as a silent canopy or open set.

Silent and open versions


Key specifications
| Prime power | 700 kVA / 560 kW |
|---|---|
| Standby power | 770 kVA / 616 kW |
| Engine | Perkins 2806A-E18TTAG4 |
| Cylinders | 6 vertical in-line |
| Aspiration | Turbocharged |
| Alternator | Leroy Somer TAL-049-B |
| Controller | DSE 7320 |
| Output | 400 V, 3 phase, 50 Hz, 1500 rpm, 0.8 power factor |
| Built-in fuel tank | 1400L |
| Noise level | 78 dB(A) ±3 dB at 7 m |
Fuel consumption
| 50% prime load | 76 L/hr |
|---|---|
| 75% prime load | 108 L/hr |
| 100% prime load | 145 L/hr |
| Standby load | 160 L/hr |
Dimensions and weight
| Silent canopy (L x W x H, weight) | 4,822 x 2,022 x 3,330 mm, 6,912 kg |
|---|---|
| Open set (L x W x H, weight) | 3,800 x 2,010 x 2,495 mm, 5,654 kg |
Data sheets
- MPS 770 generator data sheet MPS, PDF
- Perkins 2806A-E18TTAG4 engine data sheet Perkins, PDF
- Leroy Somer TAL-049-B alternator data sheet Leroy Somer, PDF
Frequently asked questions
How much diesel does a 770 kVA generator use?
The MPS 770 uses about 145 litres per hour at 100% prime load and 108 L/hr at 75% load, according to its data sheet. Real use depends on the load.
How heavy is a 770 kVA silent generator?
The MPS 770 silent canopy version weighs 6,912 kg and measures 4,822 x 2,022 x 3,330 mm.
What is the difference between 700 kVA prime and 770 kVA standby?
Prime power is for unlimited running hours at an average load of 80% of the prime rating. Standby power is for emergency backup, limited to 500 hours a year at an average 80% of the standby rating.
Get a quote for the MPS 770
Tell us your site, load and whether you need prime or standby power. Call +971 4 874 2229 or request a quote.
Also see: all Perkins generators · prime vs standby ratings · installation, AMC and spare parts
Smaller: 715 kVA Larger: 825 kVA