Prime vs Standby Generator Ratings Explained

Short answer: a prime rating is the power a generator can supply for unlimited hours as your main power source. A standby rating is the higher figure it can supply only during grid outages, for up to 500 hours a year. A 450 kVA standby generator such as the MPS 450 is rated 400 kVA prime.

The difference at a glance

Prime power (PRP)Standby power (ESP)
UseMain power source: off-grid sites, construction, remote facilitiesBackup when the grid fails: buildings, hospitals, data centres
Running hoursUnlimitedUp to 500 hours a year
Average loadUp to 80% of the prime rating over each 24 hoursUp to 80% of the standby rating over each 24 hours
Continuous runningAllowedUp to 300 hours a year
Overload10% for 1 hour in every 12 hoursNone
Rating figureLower8 to 20% higher than prime on MPS sets

Source: rating definitions on the MPS data sheets, which use the ISO 8528-1 terms PRP and ESP.

Prime and standby ratings on MPS generators

MPS 110100 kVA prime / 110 kVA standby
MPS 220200 kVA prime / 220 kVA standby
MPS 450400 kVA prime / 450 kVA standby
MPS 1000900 kVA prime / 1,000 kVA standby
MPS 20001,850 kVA prime / 2,000 kVA standby

Compare all 41 models

Which rating should you size to?

  • No grid connection, or the generator runs every day: size to the prime rating.
  • The generator only covers outages: size to the standby rating, but keep the real load near 70 to 80% of it.
  • Critical sites such as hospitals and data centres often specify extra margin or multiple synchronized sets. Check your consultant’s specification.

Common mistakes

  1. Comparing a standby kVA with another supplier’s prime kVA. Always compare like with like.
  2. Running a standby-rated set as the main power source. It will exceed its rated hours and wear faster.
  3. Ignoring heat. MPS ratings are stated at 40°C air inlet temperature. Hotter plant rooms need checking with an engineer.

Frequently asked questions

Is kVA the same as kW?

No. kW is real power; kVA includes the power factor. At the standard 0.8 power factor, kW = kVA x 0.8, so a 450 kVA standby set gives 360 kW.

Can I run a standby generator continuously?

Only for up to 300 hours a year, within the 500-hour annual limit. For longer running, choose a set sized on its prime rating.

Need help choosing?

Send us your load list and how you’ll use the generator, and we’ll recommend the right model. Call +971 4 874 2229 or request a quote.